HFR 13/16
Radial fan with direct drive or belt drive in efficiency-optimised premium version 'blue Hfan'.
Corrosion-resistant plastic centrifugal fan with housing made of thermoplastic plastic, in robust, welded design, single-sided suction, condensate discharge at the lowest point of the housing, splinter guard in accordance with safety regulations. Inspection opening on the suction side. The impeller has backward-curved blades and is statically and dynamically balanced Q6.3 (DIN ISO 21940-11). The fan frame is manufactured as strong welded galvanised steel construction.
Available in:
- Fan with direct drive. The impeller is mounted flying on the shaft of the E-motor.
- Fan with direct drive by means of a clutch.
- Fan with V-belt drive, including belt guard. The shaft is mounted in 2 block bearings
Product code | K-HFR 13/16 |
Category | Plastic |
Subcategory | Centrifugal - direct/belt driven |
Model | : | single-sided suction |
Vanes | : | Backward curved |
Flow rate | : | 3000 – 250000 m³/h |
Total pressure | : | > 5000 Pa |
Efficiency | : | tot 81 % |
Drive | : | direct/belt driven |
Temperature | : | 0-70°C |
Connection diameters | : | 18 possibilities from 160 to 1600 mm |
Material fan casing | : | PPs |
Material impeller | : | PPS - GRP - CFC - Steel coated - Stainless steel |
Motor | : | Three phase motor |
Application
- Can be used in all applications with large flow rates, such as galvanizing tanks, semiconductor industry, water treatment plants and special applications with process exhaust air
- Ideal for extracting collected exhaust air from large laboratories at universities, research institutes and in the chemical industry
- The wide range of possible materials for the housings and impellers means they can be optimally configured to meet specific requirements
Benefits
- Corrosion-resistant
- Energy efficient
- Weatherproof
- Compact design
- Wide range of accessories
- Motor outside the airflow
- Use of different motors (Ex motors) possible
ATEX versions
Explosion protected versions according to ATEX directive 2014/34/EU
Suitable as standard for installation in and extraction from ATEX zone 2, optionally for ATEX zone 1 in electrically conductive design