+32 (0)3 877 07 76
Scroll for more
vacancies

RDP

Double-inlet, direct-drive centrifugal fan. Galvanised sheet steel housing (EN10142). V - tongue in the fan outlet.

Welded impeller with 11 backward-curved aluminium blades, directly mounted on the rotor of an external permanent magnet rotor motor. No losses through belt drive. Dynamically balanced according to DIN ISO 21940-11.

High-efficiency, three-phase 5.5 kW inverter, sensorless, with EMC filter, automatic overheating protection. Inverter directly mounted on the housing and pre-configured for plug-and-play operation. No further adjustment is required.

Stepless speed control via analogue signal of 0...10 V or via Modbus RS485 interface. Drive system complete in protection class IP 54. Mains connection 400V - 50/60Hz. Maintenance free! Characteristics according to AMCA 210-07 (fig. 12) or ISO 5801 (fig. 69c and part 30.2 f).

Product code CH-RDP
Category Centrifugal - HVAC
Subcategory Double suction - AC/PM motor

 

Model : Double inlet fan
Medium : air
Flow rate  : up to  12.000 m³/h
Total pressure : up to  3.000 Pa
Drive : directly driven

 

Max temperature of pumped medium: 40°C,

Max ambient temperature : -20°C to 40°C