Box
PAF
Smoke extraction fan certified according to EN 12101-3, class F200, F300 or F400
Fan type AX integrated in the casing. The casing is made of pre-galvanized sheet steel Z275 with paint finish (stainless steel optional). The inside of the housing is insulated with rockwool covered with a heavy black fiberglass cloth.
Specifications:
Fan type AX integrated in the casing. The casing is made of pre-galvanized sheet steel Z275 with paint finish (stainless steel optional). The inside of the housing is insulated with rockwool covered with a heavy black fiberglass cloth.
Specifications:
Diameter: | 400 mm to 1250 mm |
Flow rate: | up to 120.000 m³/h |
FRB
Smoke extraction fan certified according to EN 12101-3, class F200, F300 or F400
Motorised opening box with vertical outlet. A connection is integrated in the suction opening to be connected to the mains if necessary.
The housing is made of pregalvanised steel Z275. The FRB is suitable for snowy, windy or sandy environments.
Certified for 10,000 open-close cycles. Wind resistance class WL1500 and overload resistance class SL500.
Specifications:
Diameter: | 400 mm to 1250 mm |
Flow rate: | up to 120.000 m³/h |
MPS … F4
Smoke extraction fan certified to EN 12101-3, class F400.
Casing made of galvanised sheet steel, lined with 40 mm mineral wool, non-combustible according to DIN EN 13501-1, building material class A1. The mounted mounting rails are fitted with rubber vibration dampers. Access door for cleaning and maintenance work.
The high-performance turbine with backward-curved blades is made of painted steel and is mounted on the shaft of the three-phase motor with a special shaft seal that prevents the penetration of oil and water. The turbine is dynamically balanced according to quality class G 6.3 of DIN / ISO 1940. The ball bearings are maintenance-free and are lubricated during their entire service life. Speed control possible via frequency converter. The motor is located outside the air flow and is therefore optimally protected against dirt.
Specifications:
Diameter: | 225 mm to 560 mm |
Flow rate: | up to 12.000 m³/h |
MPC … F4
Smoke extraction fan certified to EN 12101-3, class F400.
Double-walled housing made of galvanised sheet steel, lined with 30 mm mineral wool, non-flammable according to DIN EN 13501-1, building material class A1. Base plate with integrated condensate drip tray and drain plug. For cleaning and maintenance work, the inspection door can be completely removed using the door handle. The side walls can be easily removed, allowing three directions of discharge (left, right or top). The inside of the cabinet is completely smooth. The side panels are screwed into the casing frame so that no screws protrude into the casing.
Turbine with backward-curved blades, made of painted steel and mounted on the shaft of an IEC three-phase motor with a special shaft seal that prevents the penetration of oil and water. The impeller is dynamically balanced according to quality class G 6.3 of DIN / ISO 1940. The ball bearings are maintenance-free and are lubricated during their entire service life. Speed control possible via frequency converter. The motor is located outside the air flow.
Specifiactions:
Diameter: | 225 mm to 630 mm |
Flow rate: | up to 18,000 m³/h |